Fire Suppression / Fire Sprinkler

A fire sprinkler system holds water that has been standing in steel pipe, sometimes for years. It is not drinking water anymore, and on systems carrying antifreeze or foam it is considerably further from it.

Fire systems are also one of the few connections where backpressure is a given rather than a possibility. A standpipe in a multi-story building has elevation behind it and a fire pump has a great deal more, which means the system can push back toward the main without any help from a pressure drop on the street.

What is usually on one

A plain wet system with nothing added to it is commonly protected by a double check valve assembly — often a detector check, which is the same assembly with a metered bypass so the provider can see whether water is moving through a system that should be sitting still.

Add antifreeze, foam or any other additive and the classification changes to a health hazard, which takes it to a reduced pressure assembly. Fire lines also carry their own approval requirements on top of the cross-connection rules, and the assembly has to be listed for fire service — the flow characteristics matter in a way they do not on an irrigation line. This is one of the few connections where the fire marshal and the water provider both have a say, and they do not always say the same thing.

Testing one

The certification to test a backflow assembly is not application-specific — a certified cross-connection control technician can test a fire line assembly the same as any other, and we do. What makes fire line testing different is the coordination. Testing the assembly means taking fire protection out of service for the duration, which means notifying the fire department and the alarm monitoring company before the valve closes, and confirming the system is back in service afterward. On a commercial building that is a scheduled event, not a stop on a route.

When one fails

A failed assembly starts the same sixty-day clock as any other in Colorado — repaired or replaced and retested, or the supplier is required to act. On a fire line that clock is tighter than it sounds, because the two outcomes are not the same job.

Most failures are repairs, and we do those. An assembly that will not hold is usually failing on rubber: check discs, seats, springs, o-rings, a relief valve diaphragm. Those are rebuilt in place with a kit for that make and model and retested the same visit. Nothing is cut and the body stays where it is.

We do not replace assemblies inside the foundation, and a fire riser is inside the foundation. Replacement there is licensed plumbing work under Colorado's code, and on a fire service it is also work the fire marshal has an interest in. What we will do is tell you the body is finished, tell you what it has to be replaced with to satisfy both the provider and the marshal, point you to a licensed plumbing contractor, and test the new one the day it is back in service.

The reason to test early in the cycle rather than late is exactly this. A repair happens on the spot. A replacement means a second trade scheduled inside sixty days, on a system that has to come out of service to do it — a much easier phone call in March than in the last week of the clock.

We test fire line assemblies, repair them, and file the report with your provider. Schedule with enough lead time to get the notifications done properly.

Schedule a fire line test or call 970-835-9661